Midea MKA-V1200R Two Pipe Cassette Type Fan Coil | MIDEA.BG | Midea.bg
Midea MKA-V1200R Two Pipe Cassette Type Fan Coil

Midea MKA-V1200R Two Pipe Cassette Type Fan Coil

  • Type: Fan Coil;
  • Technology: Invertor Fan Coil;
  • Warranty: 36 months.

1 329,00 лв. VAT incl.

Midea MKA-V1200R Two Pipe Cassette Type Fan Coil

Midea MKA-V1200R Two Pipe Cassette Type Fan Coil delivers high heating and cooling power while delivering a modern and stylish design. The cartridge achieves low noise levels and high efficiency thanks to the DC inverter motor. The built-in condensate pump is powerful enough to lift the condensate up to 750mm. The fan coil also has a vent for fresh air outside the room.

Technical Specifications for Midea MKA-V1200R Two Pipe Cassette Type Fan Coil

Technical Specifications for Midea MKA-V1200R Two Pipe Cassette Type Fan Coil
ModelMKA-V1200R
Power supply V/Ph/Hz 220-240 / 1 / 50
Air flow (H/M/L) m3/h 1581 / 1371 / 1236
CFM 930 / 806 / 727
Cooling1 Capacity (H/M/L) kW 7.87 / 7.12 / 6.67
Water flow rate (H/M/L) m3/h 1.44 / 1.28 / 1.22
Water pressure drop (H/M/L) kPa 22.3 / 18.1 / 16.3
Power input (H/M/L) W 85 / 59 / 45
Heating2 Capacity (H/M/L) kW 9.16 / 8.54 / 7.9
Water flow rate (H/M/L) m3/h 1.73 / 1.57 / 1.46
Water pressure drop (H/M/L) kPa 28.8 / 24 / 20.7
Power input (H/M/L) W 86 / 59 / 45
Heating3 Capacity (H/M/L) kW 10.92 / 9.84 / 9.16
Water flow rate (H/M/L) m3/h 1.44 / 1.28 / 1.22
Water pressure drop (H/M/L) kPa 20 / 16.2 / 14.7
Power input (H/M/L) W 85 / 58 / 45
Sound pressure level (H/M/L) dB(A) 48 / 44 / 41
Fan motor Type DC motor
Quantity 1
Coil Row 2
Max. working pressure MPa 1.6
Diameter mm φ7
Panel Net dimensions (W х H х D) mm 950 x 45 x 950
Packing size (W х H х D) mm 1035 х 90 х 1035
Net weight kg 6
Gross weight kg 9
Body Net dimensions (W х H х D) mm 840 x 300 x 840
Packing size (W х H х D) mm 900 x 330 x 900
Net weight kg 27
Gross weight kg 33
Pipe connections Water inlet/outlet pipe inch RC3/4
Drain pipe mm ODφ32

Based on Eurovent conditions:

H: High fan speed; M: Medium fan speed; L: Low fan speed.

  1. Cooling mode (2-pipe coil): entering air temperature 27°C DB/19°C WB, entering/leaving water temperature 7°C /12°C, high fan speed.
  2. Heating mode (1): (2-pipe coil): entering air temperature 20°C DB, entering/leaving water temperature 45/40°C, high fan speed.
  3. Heating mode (2): (2-pipe coil): entering air temperature 20°C DB, enter water temperature /water flow 50°C
Cooling Capacity 7.87 / 7.12 / 6.67 kW
Heating Capacity 10.92 / 9.84 / 9.16 kW