Midea MC-SU60-RN8L chiller | Midea air conditioning systems | Midea.bg
Midea MC-SU30-RN8L air cooled scroll chiller

Midea MC-SU60-RN8L Chiller

  • Series: Midea Aqua Tempo Super II;
  • Cooling Capacity: 55 kW;
  • Heating Capacity: 62 kW;
  • Cooling EER: 2.56;
  • Heating COP: 3.10;
  • Refrigerant: R32

Ask for price: +359 32 390 100

    Aqua Tempo Super II Chillers

    Overview

    • Refrigerant R32 75% less impact on global warming;
    • DC Inverter technology allows precise consumption on real load;
    • Minimum water temperature down to 0℃ (Anti-freeze liquid needed);
    • Minimum operation ambient temperature down to -10℃ for cooling mode;
    • High energy efficiency level A++ for energy saving (Water outlet temperature at 35°C);
    • Maximum 16 units combination and controlled by one controller;
    • Maximum 960kW combination capacity;
    • Maximum 256 units controlled through Modbus;
    • Hydraulic model for customization.

    Ambient & Outlet Water Temperature

    Stable operation even under extreme conditions: -14°C to 43°C.

    Note: For cooling mode, if outlet water temperature is less than 5°C, anti-freeze liquid is needed. 0°C water temperature can be reached by changing DIP switch setting.

    High Quality Components

    DC Inverter compressor

    At the heart of the chiller lies a world-leading DC inverter compressor. The compressor’s innovative design and numerous high performance features reduce power consumption by 25%.

    1. Twin rotary structure
    2. High efficiency DC motor
    3. Highly stable moving parts
    4. Better balance and extremely low vibration

    High Efficiency Plate Heat Exchanger

    Plate heat exchanger uses metal plates to transfer heat between refrigerant and water. The fluids are exposed to a much larger surface area because the fluids spread out over the plates, so both heat transfer efficiency and heat exchanger speed are greatly improved. Multi protections including voltage protection, current protection, anti-freezing protection and water flow protection ensure system safety running.

    1. Refrigerant pipe
    2. Water pipe
    3. Water pipe
    4. Refrigerant pipe

    DC Fan Motors

    Fan speed is controlled according to the system pressure and system load, reducing power consumption by 30%. There are 32-step vector control.

    High Performance Heat Exchanger

    Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency. The specially coated blue fins enhance durability and protect against corrosion from air, water and other corrosive agents, assures a longer coil service life.

    Heat exchanger aluminum foil

    • Standard products: 200h of neutral salt mist
    • Heavy anti-corrosion products: 1000h of neutral salt mist, 140h of acid salt mist

    Heat exchanger copper pipe

    • Standard products: 24h of neutral salt mist
    • Heavy anti-corrosion products: 150h of neutral salt mist
    1. Enlarge heat-exchanging area (Fin)
    2. Enhance heat transfer (Inner-threaded pipe)
    3. High efficiency (Fin + inner-threaded pipes)

    Precise Flow Control

    Patented liquid distribution components maximize performance and minimize impact of defrosting operation. 500-step EXV with capillary tube allows stable and accurate gas flow control. Fast response results in higher efficiency and improved reliability.

    Advanced Technology

    Spray Liquid Cooling Control

    Spray liquid cooling control, which is used for enhancing heating capacity in low temperature condition.

    Precise Oil Control Technology

    Four stages of oil control technology ensure all outdoor compressor oil is always kept at a safe level, eliminating any compressor oil shortage problems.

    • Compressor internal oil separation.
    • High-efficiency centrifugal oil separator (with separation efficiency of up to 99%) ensures that oil is separated from the discharge gas and returned to the compressors in a timely fashion.
    • Oil balance pipe ensures oil distribution to keep compressor running normally.
    • Auto oil return program monitors the running time and system status to ensure reliable oil return.

    Intelligent Defrosting Technology

    The intelligent defrosting program calculates the time required for defrosting according to the actual system status, eliminating heat losses from unnecessary defrosting. A specialized defrosting valve reduces time required for defrosting to as little as four minutes.

    Rapid Cooling or Heating

    The DC inverter compressor reaches full capacity rapidly, providing quicker cooling or heating with lower levels of temperature fluctuation during the cooling/heating operation.

    Flexibility

    Modular Design

    Modularity is perfect when an extension of capacity becomes required as the building load range from 30kW to 960kW.

    High Reliability

    Alternate Defrost Operation

    By detecting the water temperature, the proportion of defrosting unit can be determined intelligently so as to realize small water temperature fluctuation during the alternate defrosting period.

    Alternative Cycle Duty Operation

    In one combination system, all units operate as alternative in cycle duty to keep equal running time, realize higher stability, better reliability and longer lifespan.

    Backup Function

    In a combination system, if one unit failed, other units can be back-up instead of the failed one for continuing operation.

    Multiple Functions

    Multiple Slient Modes

    Different silent modes enable noise reduction to suit time of day and ambient noise levels.

    • Standard mode
    • Silent mode
    • Super silent mode
    • Night silent mode

    Weather temperature curve

    With the help of weather temperature curve function, water temperature will automatically change as outside air temperature changes. When outdoor air temperature increases/decreases, the heating load will decrease/increase and water temperature will decrease/increase automatically. When outdoor air temperature decreases/increases, the cooling load will decrease/increase and water temperature will increase/decrease automatically.

    Remote alarm, on/off control, cooling/heating control.

    One-touch Water Temperature Switching

    For cooling and heating mode, different water temperatures can be switched just by one-touch.

    Anti-Corrosion Protection

    Outdoor units are given anti-corrosion treatment for non-extreme conditions as standard and can also be customized with heavy anti-corrosion treatment on main components for surface protection against corrosive air, acid rain and saline air (for installations in coastal regions) to extend machine life span. The integrity of the anti-corrosion treatment is ensured by subjecting major components and parts to salt mist testing, moisture and heating testing and light aging testing.

    Fan motor

    Standard products:

    • 72h of neutral salt mist

    Heavy anti-corrosion products:

    • 240h of neutral salt mist

    Painted sheet metal

    Standard products:

    • 500h of neutral salt mist
    • 1000h of moisture and heating test
    • 500h of light aging test

    Heavy anti-corrosion products:

    • 1000h of neutral salt mist
    • 2000h of moisture and heating test
    • 720h of light aging test

    Screws / bolts / gaskets

    Standard products:

    • 300h of neutral salt mist

    Heavy anti-corrosion products:

    • 720h of neutral salt mist

    Electric control box case

    Standard products:

    • 96h of neutral salt mist

    Heavy anti-corrosion products:

    • 240h of neutral salt mist

    Heat exchanger copper pipe

    Standard products:

    • 24h of neutral salt mist

    Heavy anti-corrosion products:

    • 150h of neutral salt mist

    Heat exchanger aluminum foil

    Standard products:

    • 200h of neutral salt mist

    Heavy anti-corrosion products:

    • 1000h of neutral salt mist
    • 140h of acid salt mis

    Convenient Control

    Touch key wired controller as standard accessory to control the chillers

    • Touch key operation
    • Parameter setting an LCD display
    • Real-time clock function
    • Multiple timer
    • Power-off memory function
    • Modbus
    • Address setting
    • Parallel function
    • Buzzer prompt tone and alarm functions
    • Weekly schedule
    • Double set point function
    • Energy saving function

    Three User Levels

    Three different user levels ensure users can easily access control functions and allow engineers convenient access to operating parameters.

    Group control for up to maximum 16 units with one wired controller

    For master unit, one controller is used for setting whilst another controller can be connected and used for monitoring.

    For slave units, controllers are only used for monitoring.

    Modbus Compatible

    Multilingual wired controller using Modbus communication protocol

    Easy Installation

    Built-in Components

    1. Hydraulic module (customization option)
    2. Water flow switch
    3. Wired controller
    4. Air purge valve
    5. Pressure relief valve

    Water Pipe Connection

    Only water piping installation is needed, no need to install refrigerant piping. 30kW model use screwed connection, while 60kW model use hoop connection. Hoop connection can be changed to flange connection by using Midea accessory in orther to suit more application.

    Rotatable electric control box with explosion-proof design

    The bottom layer can be easily achieved through the rotatable upper PCB, making the maintenance easier. Due to the micro combustibility of R32, the electric control box adopts explosion-proof design to ensure safety and reliability.

    1. Rotatable upper PCB of the electric control box
    2. Bottom layer of the electric control box
    Technical Specification for MC-SU60-RN8L Chiller
    ModelMC-SU60-RN8L
    Power supplyV/Ph/Hz380-415/ 3 / 50
    CoolingCapacitykW55
    Rated inputkW21.5
    EER2.56
    SEER4
    HeatingCapacitykW62
    Rated inputkW20
    COP3.1
    SCOP3.86
    Seasonal space heating energy efficiency classA++
    Max. input currentA40.5
    ComprossorTypeRotary
    Quantity1
    Air heat exchangerTypeFinned tube
    Motor typeDC Motor
    Quantity2
    Air flowm3/h24,000
    Water heat exchangerTypePlate
    VolumeL5.17
    Water flowm3/h9.8
    Water pressure dropkPa61
    Pump headm/
    RefrigerantTypeR32
    Charged volume3kg14
    Throttle typeEXV + Capillary
    Sound pressure level4dB(A)71.3
    Sound power level86
    Dimension (W x H x D)Net dimensionmm2220 x 1325 x 1055
    Packing dimensionmm2250 x 1370 x 1090
    WeightNet weightkg480
    Gross weightkg490
    Pipe connectionsmmDN50
    Ambient temperature rangeCooling°C-10 ~ 43
    Heating°C-14 ~ 30
    Water outlet temperature rangeCooling°C5 ~ 20
    Heating°C25 ~ 54

    Note:

    1. Cooling: Chilled water inlet/outlet Temp.12/7°C, outdoor ambient Temp. 35°C DB.
    2. Heating: Warm water inlet/outlet Temp. 40/45°C, outdoor ambient Temp. 7°C DB/6°C WB.
    3. For MC-SU60-RN8L, MC-SU60M-RN8L the total amount of refrigerant is 14 kg, including the 11.5 kg already charged before delivery and the 2.5 kg to be charged.
    4. Sound pressure level is measured at a position 1m in front of the unit and 1.1m above the floor in a semi-anechoic chamber.
    5. Capacity and efficiency data in accordance with EN14511, EN14825.
    SeriesAqua Tempo Super II
    Cooling Capacity55 kW
    Heating Capacity62 kW
    Capacity60 kW