The modular design of the MC-SU60-RN1L air cooled scroll chiller facilitates easy expansion in phases to respond to additional cooling/heating requirements. Maximum 16 units (1 main unit and 15 slave units) can be combined in one modular system to achieve maximum capacity of 960 kW. Meanwhile every separate module can be operated as main unit, also each module can be a slave unit.
If the master unit fails, all the units will stop. When the master unit fails, any of the slave one can be set as the master unit by manual setting. If one slave unit fails, this unit will stop but the others will keep running.
If master unit’s protection happens, this unit will stop but the others will keep running. If slave unit’s protection happens, this unit will stop but the others will keep running. Exceptions: PE and P9 protections. PE: Low temperature protection of evaporator. P9: Outlet and inlet water temperature difference protection.
This model can be ordered with or without hydrokit.
Model | MC-SU60-RN1L | ||
---|---|---|---|
Power supply | V/Ph/Hz | 380-415/ 3 / 50 | |
Cooling | Capacity | kW | 55 |
Rated input | kW | 22.0 | |
EER | 2.50 | ||
Heating | Capacity | kW | 61 |
Rated input | kW | 20.3 | |
COP | 3.00 | ||
Max. input current | A | 36.8 | |
Comprossor | Type | Rotary | |
Quantity | 2 | ||
Air heat exchanger | Type | Finned tube | |
Motor type | DC Motor | ||
Air flow | m3/h | 24000 | |
Water heat exchanger | Type | Plate | |
Water pressure drop | kPa | 80 | |
Water volume | L | 5.17 | |
Water flow | m3/h | 9.8 | |
Refrigerant | Type | R410A | |
Charged volume | kg | 17 | |
Throttle type | EXV + Capillary | ||
Sound pressure level | dB(A) | 72.1 | |
Dimension | Net dimension | mm | 2220 x 1325 x 1055 |
Packing dimension | mm | 2250 x 1370 x 1090 | |
Weight | Net weight | kg | 480 |
Gross weight | kg | 490 | |
Pipe connections | Water inlet/outlet | inch | DN50 |
Ambient temperature range | Cooling | °C | -15 ~ 52 |
Heating | °C | -15 ~ 30 | |
Water outlet temperature range | Cooling | °C | 0 ~ 20 |
Heating | °C | 25 ~ 55 |
Series | Aqua Tempo Super II |
Cooling Capacity | 55 kW |
Heating Capacity | 61 kW |
Compressor | Rotary |